Permit Number: T18CM10037
Parcel: 121012610

Address:
5923 E PIMA ST

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T18CM10037
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
12/28/2018 MCASTRO2 ZONING REVIEW Approved
12/28/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide cooling/heating load calculations for the proposed A/C unit.
2. Show that the proposed A/C unit meets the requirements of the 2012 IECC (e.g. thermostat, economizer. SEER, etc).
3. Correct the ventilation calculations.
12/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/28/2018 MCASTRO2 ENGINEERING REVIEW Passed
12/28/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved
12/28/2018 ROBERT SHERRY WATER REVIEW Reqs Change Determine the total proposed demand that will be served by the existing water meter. Verify that the meter is capable of meeting the demand.
12/28/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the size of the existing 1" gas piping to accommodate the new appliances.
2. A fixture drain for an automatic clothes washer shall connect to at least a 3" horizontal drain.
3. Coordinate tag numbers used in the fixture schedule and the plumbing schedule.
4. Verify that all plumbing fixtures provided by the tenant are 3rd Party listed.
12/28/2018 MARTIN BROWN FIRE REVIEW Approved
12/28/2018 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active