Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T18CM10037
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/28/2018 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 12/28/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling/heating load calculations for the proposed A/C unit. 2. Show that the proposed A/C unit meets the requirements of the 2012 IECC (e.g. thermostat, economizer. SEER, etc). 3. Correct the ventilation calculations. |
| 12/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/28/2018 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 12/28/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/28/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Determine the total proposed demand that will be served by the existing water meter. Verify that the meter is capable of meeting the demand. |
| 12/28/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Correct the size of the existing 1" gas piping to accommodate the new appliances. 2. A fixture drain for an automatic clothes washer shall connect to at least a 3" horizontal drain. 3. Coordinate tag numbers used in the fixture schedule and the plumbing schedule. 4. Verify that all plumbing fixtures provided by the tenant are 3rd Party listed. |
| 12/28/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/28/2018 | ANY | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active |