Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM10012
Parcel: 140260360

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM10012
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show the location of the HVAC diffusers on the reflected ceiling plan. There is insufficient information on the drawing to verify proper fan installation. Reference: section 107.2.1, IBC 2012.