Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not resolved. The envelope compliance certificate identifies only the changes to the windows, ignoring the exterior wall in-fills and the new doors. In addition, nothing on the drawings specifies the maximum U-value or maximum SHGC for the new fenestration. [Initial comment: Provide an energy analysis of the alterations to the building envelope. Reference: Section 101.4.3, IECC 2012.]