Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM10011
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. The envelope compliance certificate identifies only the changes to the windows, ignoring the exterior wall in-fills and the new doors. In addition, nothing on the drawings specifies the maximum U-value or maximum SHGC for the new fenestration. [Initial comment: Provide an energy analysis of the alterations to the building envelope. Reference: Section 101.4.3, IECC 2012.] |