Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM10011
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/27/2018 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 12/27/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a source of make up air (e.g. a door louver) for the dryer installation to comply with Section 504.5, IMC 2012. 2. Provide an energy analysis of the alterations to the building envelope. Reference: Section 101.4.3, IECC 2012. |
| 12/27/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/27/2018 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 12/27/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/27/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/27/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/27/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/28/2018 | MASHFOR1 | FIRE | REVIEW | Approved |