Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09928
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Code Review: The occupant load is calculated using a 100 SF/occupant for a Business (B) occupancy classification. Per the IBC Table 1004.1.2, the occupant load should be based on the function of the space. Typically, clubhouse function will be for gathering of persons for civic, social, or recreational purposes (Assembly). Please recalculate the occupant load for this use. You can break the space down into individual use areas (kitchen, office, lobby, etc.), but the occupant load will most likely exceed 15 occupants, thus affecting the number of required restrooms for the building. An appeal to the Building Official for one restroom (allowing only 15 occupants in the space) would be required. 2. Sheet A1; Code Review: Please address the requirements for a drinking fountain and a service sink according to the IBC Table 2902.1. 3. Sheet A3; Floor Plan: Please indicate the sink/countertop height in the kitchen as 34" above finish floor for accessibility.4. 4. Sheet A3; Floor Plan: Please indicate the hardware for exterior doors F and G. 5. Sheet A3; Floor Plan: The sliding barn door (I) is part of the means of egress (exiting from the leasing office), and must therefore meet the requirements of the IBC Section 1008.1.4.3. Please verify. 6. Sheet A3; Floor Plan: The elevation reference indicated in the restroom should be A4. Please revise. 7. Sheet A3; Floor Plan: Please indicate exterior elevation C/A6 on the south wall. 8. Sheet A3; Floor Plan: Please revise the exterior elevation references to Sheet A6 (A, B, C, and D). 9. Sheet A3; Floor Plan: Please revise the building section references to Sheet A7 (1, 2, and 3). 10. Sheet A3; Floor Plan: Please revise Sections 3 and 4 (at the new masonry walls) to Sheet A8. 11. Sheet A4; Detail 3: Please indicate on the detail the slab and footing are existing. 12. Sheet A8; Details 1, 2, 5, 6, and 7: Please reference these details on a building plan or section. 13. Sheet S1; Structural Notes (Materials Specifications): Please include masonry in these specifications (new walls per Sheet A3). 14. General: Please provide a Special Inspection Certificate with Parts A and B completed. 15. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |