Permit Number: T18CM09927
Parcel: 30503004B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09927
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2019 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/04/2019 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses and corrected plan sheets to all review comments:
1. SHT. 15 Buildings used in the treatment of potable water facilities are assigned to Risk Category III per IBC TABLE 1604.5. The risk category assigned to this project is in Risk Category I. Please assign the proper risk category for this project.
2. Page 4 of the structural calculations REVISIONS 2/20/2018 specifies 4000 psi concrete tor the elevated roof design. This specification should be noted on the CONCRETE section of the GENERAL STRUCTURAL NOTES. IBC 107.2.1.
01/11/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/11/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/11/2019 ROBERT SHERRY WATER REVIEW Passed
01/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/23/2019 DAVID RIVERA ZONING REVIEW Approved
01/28/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved
12/26/2018 MASHFOR1 FIRE REVIEW Approved