Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09927
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2019 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/04/2019 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses and corrected plan sheets to all review comments: 1. SHT. 15 Buildings used in the treatment of potable water facilities are assigned to Risk Category III per IBC TABLE 1604.5. The risk category assigned to this project is in Risk Category I. Please assign the proper risk category for this project. 2. Page 4 of the structural calculations REVISIONS 2/20/2018 specifies 4000 psi concrete tor the elevated roof design. This specification should be noted on the CONCRETE section of the GENERAL STRUCTURAL NOTES. IBC 107.2.1. |
| 01/11/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/11/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/11/2019 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 01/17/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/23/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/28/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 12/26/2018 | MASHFOR1 | FIRE | REVIEW | Approved |