01/14/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the dimensions of the primary scupper and the downspout. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.
01/14/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Specify that the maximum U-factor and maximum SHGC values for the fenestration products shall be NFRC-certified. Reference: Section C303.1.3, IECC 2012.
2. The insulation requirement for mass walls for Zone 2 requires R5.7 continuous insulation. The batt insulation specified in detail 9/A6 is not continuous insulation. Provide calculations to show that the specified mass wall has a maximum U-value of 0.142. Note that there are two independent wall types: above the dropped ceiling and below the dropped ceiling. Reference: Sections C402.1 and C402.1.2, IECC 2012.
3. Revise the heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.
4. Verify that the point load caused by the new condensing unit will not over-stress the existing roof. Reference: Section 302.1, IMC 2012.
5. Provide structural calculations and details to show how the fan coil unit is to be connected to the building structure. Reference: Section 302.1, IMC 2012.
01/14/2019 ROBERT SHERRY WATER REVIEW Reqs Change Verify the size and serial number of the water meter serving this address; meter number 15783424 is associated with 3001 E Drachman. State the total water demand served by the water meter for this address.
01/16/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
1. Ref: Plan Sheet E2 (lighting). Provide full compliance with the Tucson/Pima County Outdoor Lighting Code (OLC) for the exterior lighting. Sec 104.1 OLC
12/21/2018 MCASTRO2 ENGINEERING REVIEW Passed
12/21/2018 MCASTRO2 ZONING REVIEW Approved
12/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/21/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/26/2018 MASHFOR1 FIRE REVIEW Approved