Permit Number - T18CM09917
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2019 KROBLES1 BUILDING-RESIDENTIAL REVIEW Needs Review
12/20/2018 MCASTRO2 ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Mark Castro,
Lead Planner

PROJECT:
T18CM09917
2034 E 7th St
Carport to Garage Conversion


TRANSMITTAL: December 20, 2018


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 10'-8", the required setback to the south lot line is 7', the proposed setback is 2'-6"

Based on a wall height of 10'-8", the required setback to the east lot line is 7', the proposed setback 1'-4".

DDO approval required prior to zoning approval.
12/20/2018 MCASTRO2 ENGINEERING REVIEW Passed