Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM09905
Parcel: 10511028B

Address:
17 W WETMORE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM09905
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that a receptacle outlet is provided for each fan coil unit located in the interstitial space of a floor-ceiling assembly (e.g. above a hard ceiling). Provide a light fixture for fan coil maintenance on the 2nd & 3rd floors above hard ceilings. Reference: Sections 306.4 and 306.4.1, IMC 2012.]