Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM09905
Parcel: 10511028B

Address:
17 W WETMORE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM09905
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/08/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify the capacities of fan-coils 1,10, 11, 12, 13, 16, 17, 19, 21, and 29. The cooling capacities seem to be much greater than the load calculations will support. [Initial comment: Clarify how the zones used for the cooling/heating load calculations can be compared to the capacities for the split system heat pumps.]
2. Show the maintenance access panel locations and the maintenance receptacles for the fan-coils located over hard ceilings. [Initial comment: Verify that maintenance access, lighting, and a receptacle outlet are provided for each fan coil unit located in the interstitial space of a floor-ceiling assembly (e.g. above a hard ceiling). Reference: Sections 306.4 and 306.4.1, IMC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2019 AVAUGHN1 APPROVAL SHELF Completed
02/20/2019 AVAUGHN1 OUT TO CUSTOMER Completed
02/20/2019 AVAUGHN1 REJECT SHELF Completed