Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM09905
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/08/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the capacities of fan-coils 1,10, 11, 12, 13, 16, 17, 19, 21, and 29. The cooling capacities seem to be much greater than the load calculations will support. [Initial comment: Clarify how the zones used for the cooling/heating load calculations can be compared to the capacities for the split system heat pumps.] 2. Show the maintenance access panel locations and the maintenance receptacles for the fan-coils located over hard ceilings. [Initial comment: Verify that maintenance access, lighting, and a receptacle outlet are provided for each fan coil unit located in the interstitial space of a floor-ceiling assembly (e.g. above a hard ceiling). Reference: Sections 306.4 and 306.4.1, IMC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/20/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 02/20/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 02/20/2019 | AVAUGHN1 | REJECT SHELF | Completed |