| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Site Sheet: This project was originally processed with five separate parking structures with a total of 10,854 SF. This site plan, as well as the structural sheets and calculations, indicate only two structures. Please verify. 2. Site Sheet: Please indicate on this sheet the distance from the edge of the roof to the property line for each structure. 3. Structural Calculations: Calculations were not located for the drilled pier design. Please verify and provide. 4. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |