Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM09900
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2019 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/16/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses to all plan review comments. 1. Specify the height of the covered parking structure at the lowest point of the roof framing members. The clear height for vehicle and pedestrian areas cannot be less than 7 ft. IBC 406.4.1. 2. The SPECIAL INSPECTION CERTIFICATE must be filled in, sealed and submitted before the building permit can be issued. IBC 1704. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/16/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |