Permit Number: T18CM09900
Parcel: 128100810

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM09900
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2019 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/16/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments.
1. Specify the height of the covered parking structure at the lowest point of the roof framing members. The clear height for vehicle and pedestrian areas cannot be less than 7 ft. IBC 406.4.1.
2. The SPECIAL INSPECTION CERTIFICATE must be filled in, sealed and submitted before the building permit can be issued. IBC 1704.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2019 AMARTIN1 OUT TO CUSTOMER Completed