Permit Number: T18CM09867
Parcel: 13101002L

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM09867
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2019 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses and corrected plans or calculations to all plan review comments:
1. 1. Sheets S3, S5 and S7 item #3 all make reference to STEEL COLUMN PER TABLE THIS SHEET; the referenced table is not shown on the sheets. Please provide referenced tables. IBC 107.2.1
2. Sheets S3, S4 PANEL TEE SECTION drawings. Provide the EQ dimensions from Nodes 3 and 4 to the centerline of column and drilled pier so that the shade structures can be referenced back to the Steel Frame Model Info and Base Reactions contained in the Structural Calculations. IBC 107.2.1.
3. The structural members shown on the Steel Frame Model Info and Base Reactions do not match the sizes of framing members on the structural plans. Indicate the specific shade structure on the plans for each Steel Frame Mode Info and Base Reaction drawing in the structural calculations.
01/07/2019 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2019 AMARTIN1 OUT TO CUSTOMER Completed