Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2.1 notes Keynotes 11 , 18 , and 19 on First Floor Plan , but are not listed under Keynotes . IBC 107.2.1.
06/06/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the heating/cooling load calculations for the new heat pumps.
2. Update the mechanical code compliance certificate on sheet M1.1 to include the three new heat pumps.
06/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/06/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the changes made to the roof drainage that led to the relocation of the roof drains.