Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM09841
Parcel: 123020860

Address:
2500 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM09841
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2.1 notes Keynotes 11 , 18 , and 19 on First Floor Plan , but are not listed under Keynotes . IBC 107.2.1.
06/06/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the heating/cooling load calculations for the new heat pumps.
2. Update the mechanical code compliance certificate on sheet M1.1 to include the three new heat pumps.
06/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/06/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the changes made to the roof drainage that led to the relocation of the roof drains.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2019 AVAUGHN1 APPROVAL SHELF Completed
06/11/2019 AVAUGHN1 OUT TO CUSTOMER Completed
06/11/2019 AVAUGHN1 REJECT SHELF Completed