Permit Number: T18CM09841
Parcel: 123020860

Address:
2500 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM09841
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2019 MARTIN BROWN FIRE REVIEW Approved
04/12/2019 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/12/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. Provide economizers for the proposed heat pumps or explain how restaurants and mercantile occupancies require humidity controls. Identify the ASHRAE 90.1 compliance path that is being employed. [Second comment: The COMcheck analysis uses humidity-control requirements as a reason for not installing economizers. What are the humidity-control requirements for restaurants and mercantile occupancies? Identify which compliance path the HVAC design is using, simplified or mandatory. Reference: Section 6.2.1, ASHRAE 90.1-2010.] [Initial comment: The architect has selected ASHRAE 90.1-2010 as the method for showing compliance with the adopted energy code. Provide calculations that demonstrate compliance with the HVAC requirements of ASHRAE 90.1-2010 (e.g. COMcheck). Reference: Section C401.2 (1), IECC 2012.]
04/15/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/15/2019 ROBERT SHERRY WATER REVIEW Completed
04/30/2019 DAVID RIVERA ZONING REVIEW Approved
05/02/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved
05/03/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved Please provide IECC code compliance for the lighting. If the interior lighting is temporary untill the buildout for the tenant spaces, address this with a note on the lighting plan.
Ref; 2012 IBC sec 107.2.1, 2012 IECC.