Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T18CM09841
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/12/2019 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/12/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. Provide economizers for the proposed heat pumps or explain how restaurants and mercantile occupancies require humidity controls. Identify the ASHRAE 90.1 compliance path that is being employed. [Second comment: The COMcheck analysis uses humidity-control requirements as a reason for not installing economizers. What are the humidity-control requirements for restaurants and mercantile occupancies? Identify which compliance path the HVAC design is using, simplified or mandatory. Reference: Section 6.2.1, ASHRAE 90.1-2010.] [Initial comment: The architect has selected ASHRAE 90.1-2010 as the method for showing compliance with the adopted energy code. Provide calculations that demonstrate compliance with the HVAC requirements of ASHRAE 90.1-2010 (e.g. COMcheck). Reference: Section C401.2 (1), IECC 2012.] |
| 04/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/30/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/02/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 05/03/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Please provide IECC code compliance for the lighting. If the interior lighting is temporary untill the buildout for the tenant spaces, address this with a note on the lighting plan. Ref; 2012 IBC sec 107.2.1, 2012 IECC. |