Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM09841
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2019 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Coordinate the water service (i.e. meter size) to the building with the civil design. Show the location of the backflow valves on the civil plans. |
| 01/08/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS; Occupancy Information: The information relative to occupancy uses, occupant loads, and exiting will not be reviewed at this time as this is a shell permit only. Those issues will be reviewed as each tenant space is occupied (first tenant in). 2. Sheet TS (Occupancy Information); Sheet A1.1 (Floor Plan): The information on Sheet TS indicates three tenant spaces, while the Floor Plan on Sheet A1.1 indicates five spaces. Please coordinate. 3. Sheet TS; Notes: Note 2 indicates several special inspections required. Please coordinate these with the structural engineer, and remove the inspections that are not required. 4. Sheet GN2; Accessibility Details: The title for Details 1 and 2 indicates the 2010 ADA Standards. Please revise to the 2009 ICC/ANSI A117.1, and revise details as required. 5. Sheet GN2; Water Closet Side Wall Grab Bars: Please locate the vertical grab bar from the back wall per the ICC/ANSI Figure 604.5.1. 6. Sheet A1.1: This sheet requires the seal of a registered design professional per the requirements of the 2012 IBC Section 107. 7. Sheets A1.1, A1.2, A2.1, A2.2, A2.3, A3.1, A3.2, A4.1, A4.2, A5.1, A5.2, and A5.3: Please remove System Notes that are not applicable to the information on those sheets. 8. Sheet A1.3; Site Data (Fire Sprinklers): The drawing indicates an NFPA-13R automatic fire sprinkler system per the IBC Section 903.3.1.2. That system is for Group R occupancies only. This automatic sprinkler system must meet the requirements of the IBC Section 903.3.1.1. Please revise. 9. Sheet A1.3; Site Data (Occupant Loads and Exits): These issues will not be reviewed for this shell only permit. 10. Sheet A1.4; Site Lighting Pole Detail: This will not be reviewed until the maximum pole height is determined. A structural engineer will be required to submit structural calculations for the pole foundation design. 11. Sheet A2.1; Wall Schedule: Please remove all wall designations that are not pertinent to this plan. 12. Sheet A3.2; Finishes: Please add F2 to the wall finishes. 13. Sheets S1.1, S2.1, and S2.2; Wall Footings: The drawings indicate a 10" x 1'-4" wall footing, while the structural calculations (Page 49) indicate a 12" x 1'-4" footing. Please coordinate. 14. Sheets S1.1, S2.1, and S2.2; Plans: Please provide north arrows on the plans. 15. Sheet S2.1; Framing Plan: The plan indicates S1 roof trusses, while the System Notes indicate R1. Please coordinate. 16. General: Please provide a Special Inspection Certificate with Parts A and B completed. 17. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 01/08/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the labeling of the grease waste lines to agree with the plumbing symbol and legend (currently labeled as "W" instead of "GW"). 2. Revise sheet P2.1 to show the cut-off section of the North end of the building. 3. Provide cleanouts for the 4" roof drain and overflow drain leaders per Section 708.3, IPC 2012. Reference: Section 1101.8, IPC 2012. |
| 01/08/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The architect has selected ASHRAE 90.1-2010 as the method for showing compliance with the adopted energy code. Provide calculations that demonstrate compliance with the HVAC requirements of ASHRAE 90.1-2012 (e.g. COMcheck). Reference: Section C401.2 (1), IECC 2012. 2. Correct the EER values for heat pumps HP-1, 2, 3, 4, 5, 6, 7, 8, 9, and 10 (The value shown is the IEER for each unit). Reference: Section 107.2.1, IBC 2012. 3. Include the R-value of the cavity insulation for the exterior walls in the wall descriptions. Reference: Section 107.2.1, IBC 2012. 4. Provide the R-value of the proposed roof insulation in the roof description. Reference: Section 107.2.1, IBC 2012. 5. Provide the supporting documentation for the performance of the specified fenestration components (see footnote b of the COMcheck assembly descriptions). |
| 01/10/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1) Sheet A1.3 references IBC section 903.3.1.2, NFPA 13R. Should be section 903.3.1.1, NFPA 13. Please revise. 2) Please clearly indicate where panic hardware will be located. 3) Sheet P1.1 indicates a design density of .15, correct density should be .20. Please revise. |
| 01/14/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/18/2019 | NICHOLAS ROSS | ZONING | REVIEW | Reqs Change | DP18-0195 must be approved first. |
| 01/22/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | 1) Once the DP has been approved and any outstanding commercial review comments have been addressed, Engineering can conduct an over the counter review of the building plans. Call or Email to Schedule John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/31/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 01/31/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 01/31/2019 | QJONES1 | REJECT SHELF | Completed |