Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM09840
Parcel: 11504602G

Address:
880 E 2ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM09840
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/07/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The specification sheet for the faucet does not indicate that the temperature control is listed to ASSE 1070. [Initial comment: Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Section 607.1.2, IPC 2012.]
2. The floor sink in plan 2/P-4.02 and the new floor drain in plan 4/P-4.01 appear to have vents running horizontally below the floor (the flood rims for both fixtures are at floor level). [Initial comment: Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (see plan 2/P-4.02). Reference: Section 905.4, IPC 2012.]
03/07/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Keynotes 11, 12, 13, and 14 are still shown on sheet M-2.00 but are not described. [Initial comment: Describe the keynotes 10, 11, 12, 13, 14, and 45 used on the second sheet M-2.00. Reference: Section 107.2.1, IBC 2012.]
2. Codes that are unique to California are still included in the notes on sheets M-1.00 and M-2.00. Simply changing the name of the code to an international code doesn't work unless the code sections are also changed. In addition, Title 24 and the "Green Code" are not recognized in the City of Tucson. [Initial comment: Revise the California Code callouts to the International Codes adopted by the City of Tucson. Reference: Section 107.2.1, IBC 2012.]
3. Domestic clothes dryers require exhaust ducts that are 4" in diameter and are limited in length. See Sections 504.6 and 504.6.4.1, IMC 2012. [Initial comment: Clarify nature of the proposed clothes dryers: are they commercial or domestic? If the dryers are commercial, provide the manufacturer's installation instructions for reference and show that the exhaust ducts comply with Section 504.7, IMC 2012 for support, clearances and length. If the clothes dryers are domestic, provide exhaust ducts that comply with Section 504.6, IMC 2012.]
03/18/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E-2.04.1. Provide the following:
(a) Per the notes to table 401.1. "Use any one of the three options, 1, 2, or 3."
(b) The Outdoor Lighting Code does not define "CUT OFF" for shielding. The luminaire shielding is either Full Cut-Off or Unshielded. The lumen calcs on the plan have a column for "Cut Off". This would not be applicable.
(c) Show total allowed lumens shielded and unshielded VS total proposed lumens (include existing).
(d) Indicate whether a special inspection is required or not. Sec 104.2.2, 106.2.1.
2. Ref; Plan Sheet E-5.00. The ampacity rating and the OCPD for panel 2L does not correlate between the panel schedule and the single line diagram. Please clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.