Permit Number: T18CM09840
Parcel: 11504602G

Address:
880 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09840
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2019 MARTIN BROWN FIRE REVIEW Approved
01/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-0.01; Supplemental Bids: If bid alternates are to be included with this permit, revisions to the approved/issued drawings must be submitted for review and approval by the City of Tucson.
2. Sheet A-0.08; Accessible Water Closet Details 4 and 5: Please add the vertical grab bar to the detail elevations per the ICC/ANSI Figure 604.5.1.
3. Sheet A-0.10; Keynotes: Note 8 was not located on the plan. Please verify. New canopies will require new structural drawings and calculations.
4. Sheet A-0.21; Door Schedule Legend: This indicates the door hardware schedule is in Section 08700 of the project manual. Please revise this reference to Sheet A-0.22.
5. Sheet A-2.03; Floor Plan: Per the IBC Section 1108.2.9.1, dining surfaces for the consumption of food and drink must provide a minimum of 5% that are accessible. On this sheet, please provide a calculation of the total number of dining surfaces and the required number of accessible dining surfaces, along with the actual number of accessible dining surfaces. Indicate those surface locations on this plan.
6. Sheet A-2.04; Floor Plan: A plan reference at the registration area indicates 1A/A-6.01. There is no 1A plan. Please revise the reference.
7. Sheet A-2.11; Floor Plan 1: Please provide the wall types at the new walls indicated on the plan.
8. Sheet A-3.03; Elevations 1A and 2A: The horizontal grab bar indicates 12" from the water closet centerline to the side wall. Please revise that dimension per the ICC/ANSI Figure 604.5.2.
9. Sheet A-3.05; Elevations 1A and 2C: The horizontal grab bar indicates 12" from the water closet centerline to the side wall. Please revise that dimension per the ICC/ANSI Figure 604.5.2.
10. Sheet A-3.07; Elevations 1A and 2C: The horizontal grab bar indicates 12" from the water closet centerline to the side wall. Please revise that dimension per the ICC/ANSI Figure 604.5.2.
11. Sheet A-5.02; Detail 5: Please indicate the metal stud spacing and size.
12. Sheet A-5.03; Details 4, 7, and 8: Please indicate the metal stud spacing and size.
13. Sheet A-6.08; Details 3D and 3E: Per the IBC Section 1109.3, sinks available for public use must be accessible as required. Please verify the height of the counters should be 2'-10" maximum above finish floor.
14. Sheet S-1.01; General Structural Notes (Steel Stud Framing): In Note 9, please finish the "joists" size.
15. Sheet S-2.00; Overall Plan: An enlarged plan reference at the bar indicates 1/S2.01. Please revise that reference.
16. Sheet S-2.00; Overall Plan: Please indicate on this plan reference to the enlarged plans on Sheet S-2.01.
17. Sheet S-2.01: Please provide structural calculations and additional details for the screen wall structure and foundations, the water fountain structure and foundations, the cantilevered canopy structure and foundations, and the cantilevered ceiling structure and foundations.
18. Sheet S-2.01 (Keynote 1); Sheet S-3.01 (Detail 103): The detail indicates tube columns at 5'-6" o.c. maximum (Note 4), while the Keynote 1 indicates 6'-0" o.c. maximum. Please coordinate.
19. Sheet S-2.02; Pergola Plans: Please provide structural calculations for the pergola framing and foundations.
20. Sheet S-2.02; Foundation Plan Keynotes: Note 4 references Detail 4-C. Please revise that reference to Detail 104.
21. Sheet S-2.02; Foundation Plan: Please show all new footings the same physical size.
22. Sheet S-3.01; Detail 101: A 6" dimension is indicated at the bottom of the tube column. Please clarify.
23. Sheet S-3.01; Detail 103: Please provide a column base plate size and anchor bolt size.
24. Sheet S-3.01; Detail 104: Please provide the tube column base plate size and anchor bolt size.
25. Sheet S-4.01; Detail 205: Please provide structural calculations for the steel lintel at the new opening in the masonry wall.
26. General: Please provide the Special Inspection Certificate with Parts A and B completed.
27. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Constact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
01/08/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the outer circle of the registrant's seal shall be 1-1/2" in diameter, +/- 1/16". See Appendix A of the Rules of the Arizona State Board of Technical Registration for further information regarding seals.
2. Describe the keynotes 10, 11, 12, 13, 14, and 45 used on the second sheet M-2.00. Reference: Section 107.2.1, IBC 2012.
3. Revise the California Code callouts to the International Codes adopted by the City of Tucson. Reference: Section 107.2.1, IBC 2012.
4. Clarify nature of the proposed clothes dryers: are they commercial or domestic? If the dryers are commercial, provide the manufacturer's installation instructions for reference and show that the exhaust ducts comply with Section 504.7, IMC 2012 for support, clearances and length. If the clothes dryers are domestic, provide exhaust ducts that comply with Section 504.6, IMC 2012.
01/08/2019 ROBERT SHERRY WATER REVIEW Completed
01/09/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the outer circle of the registrant's seal shall be 1-1/2" in diameter, +/- 1/16". See Appendix A of the Rules of the Arizona State Board of Technical Registration for further information regarding seals.
2. Provide a legible copy of sheet P-3.01 (the screened background is too faint). Reference: Section 107.2.1, IBC 2012.
3. Provide a floor drain for the laundry room. Reference: Section 412.4, IPC 2012.
4. Verify that the specified electronic faucet for the public lavatories will dispense a maximum of 0.25 gallons per metering cycle and that the cycle will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
5. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Section 607.1.2, IPC 2012.
6. The shop drawings for the water feature calls for the installation of a reduced pressure principle backflow prevention assembly for the water makeup to the fountain. Where is the backflow preventer located?
7. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
8. Water supply connections to beverage dispensers (e.g. coffee brewers, espresso machines) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
9. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
10. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (see plan 2/P-4.02). Reference: Section 905.4, IPC 2012.
01/15/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide sealed Electrical plans as required per Arizona Revised Statutes and Board of Technical Registration, R4-304. "** ENGINEERS MUST LIST BRANCH -Agriculture, Architectural Chemical, Civil, Control Systems, Electrical, Environmental, Fire Protection, Geological, Industrial, Mechanical, Metallurgical Mining, Nuclear, Petroleum, Sanitary, or Structural". The electrical plans need to be sealed by an Electrical Engineer registered in the State of Arizona.
2. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. See section 104 for plan submittal requirements. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd.
3. Ref: Plan Sheet E2.02. The symbols representing electrical devices are to small and some not legible. Please enlarge so as to distinguish and correlate with the symbols plan.
4. Ref: Plan Sheet E2.04.
(a) There are lines or branch circuiting on the floor plan borders and through-out the lighting plan that are not connected to luminaires or devices, do not continue, or there is no branch circuit designations. Please clarify.
(b) Designate a symbol or mark for each luminaire that correlates with the Luminaire Schedules, Lighting Control Schedule, and the IECC Comcheck Certificate.
(c) Ref: Plan Sheet E2.04 and E3.00. There is a statement below the Keynotes-New P.A box. "Some Keynotes may not apply to all sheets". For clarity please remove the keynotes that do not apply to the corresponding sheet.
(d) The lighting in the restrooms do not correlate with the lighting schedules, or are not identified in the lighting schedule and have incomplete branch wiring. Please clarify.
(e) Some of the notes and or symbols in the restrooms are overlapping making it difficult to determine what its identifying or representing.
5. Ref: Plan Sheet E211. Designate a branch circuit and panel for the outlets in the Meeting Room and correlate with the corresponding panel schedule. 2017 NEC 408.4.
6. Ref: Plan sheet E3.00.
(a) Electrical Schedule. Define on the plan what the abbreviations "SR", "VFY", and "EC" represent.
(b) Ref: 'Open Cooking' and 'Lobby Bar'. Identify the devices or symbols shown as the circle with the line through it. Correlate with the symbols plan.
7. Ref: Plan Sheet E5.00.
(a) Provide a load calc summary for the existing service. Include all the panels.
(b) Include the size for all the OCPD's shown on the line diagram. (Panel 'B' and 'C')
(c) The panel schedule for panel 'B' is not showing the OCPD for panel '1L'. Update the load calcs accordingly.
(d) Panel 'B'. Designate a OCPD for the Bar Receptacle ckt#30.
(e) Panel 'C' schedule is not showing the OCPD for panel '2L'. Update the load calcs accordingly.
(f) Why is panel 'EPL' not included in the one line diagram? If fed from a different source, please indicate and provide a complete line diagram with load calcs, as it appears there are new loads added to this panel.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd.
Dan Santa Cruz,
Commercial Electrical Plan Review, City of Tucson
Dan.santacruz@tucsonaz.gov
01/22/2019 STEVE SHIELDS ZONING REVIEW Approved
01/25/2019 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2019 AVAUGHN1 APPROVAL SHELF Completed
02/21/2019 AVAUGHN1 OUT TO CUSTOMER Completed
02/21/2019 AVAUGHN1 REJECT SHELF Completed