Permit Number: T18CM09835
Parcel: 12902049E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09835
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2018 ELISA HAMBLIN ZONING REVIEW Approved
12/18/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the HVAC air distribution to avoid using the egress path as a duct. Reference: Section 601.2, IMC 2012.
2. Show how the flexible air ducts are to be supported. Reference: Section 603.10, IMC 2012.
12/18/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/18/2018 EHAMBLI1 ENGINEERING REVIEW Passed
12/18/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/18/2018 ROBERT SHERRY WATER REVIEW Completed
12/18/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/18/2018 MASHFOR1 FIRE REVIEW Approved
12/18/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed