Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09835
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2018 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
| 12/18/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the HVAC air distribution to avoid using the egress path as a duct. Reference: Section 601.2, IMC 2012. 2. Show how the flexible air ducts are to be supported. Reference: Section 603.10, IMC 2012. |
| 12/18/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/18/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 12/18/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/18/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/18/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/18/2018 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 12/18/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |