Permit Number: T18CM09775
Parcel: 128010040

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM09775
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The Tucson/Pima County Outdoor Lighting Code is Calculated using total lumen output and lamp color temperature not wattage. Please revise the lighting calcs to reflect lumens not wattage.
2. Ref: Tucson Outdoor Lighting Code, 2012 IBC sec 107.2.1