Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet PV 9.0. Note 1 in the LUMINAIRE SCHEDULE and the note at the luminaire locations calls out for a new lighting circuit and new timer or photo cell to operate the under canopy lighting. "Pick up 120vac from a convenient location" is not acceptable. Assign a branch circuit and panel for the lighting. Indicate the location of the panel on the plans and verify the panel has a spare circuit for the lighting. Also indicate the locations of the timer and or the photo cell.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements.
01/08/2019 MARTIN BROWN FIRE REVIEW Approved
01/14/2019 LOREN MAKUS ENGINEERING REVIEW Passed
01/14/2019 STEVE SHIELDS ZONING REVIEW Passed
12/26/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved