Permit Number: T18CM09735
Parcel: 12711081A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09735
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2019 ELISA HAMBLIN ZONING REVIEW Approved
01/29/2019 EHAMBLI1 ENGINEERING REVIEW Passed
01/29/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a elctrical plan sealed by an engineer registered in the state of Arizona. Designate circuits and panel for the lighting and power, OCPD's, Conductor sizes and types.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirenents
05/29/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Passed
05/29/2019 PMARTIN1 BUILDING-COMMERCIAL REVIEW Needs Review
05/29/2019 PMARTIN1 FIRE REVIEW Needs Review
05/29/2019 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Approved
05/29/2019 RMCCOY1 WATER REVIEW Passed
05/29/2019 PMARTIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review