Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09734
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2018 NICHOLAS ROSS ZONING REVIEW Approved
12/13/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change PROVIDE HEATING/COOLING LOAD CALCULATIONS
12/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/13/2018 NROSS1 ENGINEERING REVIEW Passed
12/13/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Occupant Load: The Club House uses 100 SF/occupant. The IBC Table 1004.1.2 indicates 15 SF/occupant for an assembly area. That Table is based on the function of the space. Please verify.
2. Sheet A3; Floor Plan: Plan Notes 4, 10, 11, 12, and 13 were not located on the plan. Please verify.
3. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
12/13/2018 ROBERT SHERRY WATER REVIEW Completed
12/13/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/13/2018 JVINCEN1 FIRE REVIEW Approved
12/13/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/18/2018 QJONES1 LANDFILL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2018 QJONES1 APPROVAL SHELF Completed
12/18/2018 QJONES1 OUT TO CUSTOMER Completed
12/18/2018 QJONES1 REJECT SHELF Completed