Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09734
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2018 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 12/13/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | PROVIDE HEATING/COOLING LOAD CALCULATIONS |
| 12/13/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2018 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 12/13/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Occupant Load: The Club House uses 100 SF/occupant. The IBC Table 1004.1.2 indicates 15 SF/occupant for an assembly area. That Table is based on the function of the space. Please verify. 2. Sheet A3; Floor Plan: Plan Notes 4, 10, 11, 12, and 13 were not located on the plan. Please verify. 3. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb |
| 12/13/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/13/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/13/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 12/13/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/18/2018 | QJONES1 | LANDFILL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 12/18/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 12/18/2018 | QJONES1 | REJECT SHELF | Completed |