Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2020 MARTIN BROWN FIRE REVIEW Approved
03/26/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide details of exterior patio Fixed seating , connections , locations , etc. IBC 10.
2. Illustrate the egress travel through the patio and illustrate the exits from the patio. IBC 10.
3. Provide details of interior Fixed seating , connections , locations , etc. IBC 10.
4. Sheet G1.0 - Occupant Load - specifies fixed seating indoor and outdoor , but sheet A1.2 specifies standard table and chair for outdoor and indoor , clarify and amend plan and occupant load if necessary. IBC 10.
5. Provide a complete code analysis for the mininum number of required plumbing fixtures . IBC 29.
6. Provide the valuation for the tenant improvement .
7. Include Second floor in the Egress Plan and Occupant Load analysis .IBC 10.
8. Provide dimensions for Mens and Womens restrooms and illustrate ADA compliance. IBC 107.2.1.

Respond to plan review comments in writing .
04/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope and the addition of the new rooftop units. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.
2. Alterations of an existing building in which the existing ceiling or wall cavities are exposed, shall have the exposed cavities filled with insulation. Reference: Section 101.4.3, IECC 2012.
3. Provide heating and cooling load calculations, using the exterior design conditions shown in Section C302.2, IECC 2012, as modified by the City of Tucson.
4. Show the size, routing, and termination of the condensate drains for the new rooftop units. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
5. Provide the size of the exhaust duct for the hood H-2. Reference: Section 107.2.1, IBC 2012.
6. Coordinate the exhaust and make-up air flow rates shown on the grease hood schedule, exhaust fan ventilation schedule, make up air equipment schedule, and the mechanical plan. Reference: Section 107.2.1, IBC 2012.
7. Detail 2/M2.0 is labeled as an existing hood. Isn't the hood new? Reference Section 107.2.1, IBC 2012.
8. Provide structural details as required for any special framing revisions needed for the roof penetrations of the 20" x 18" exhaust ducts. Reference: Section 302.1, IMC 2012.
9. Provide structural calculations to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
10. The practice of using grease duct enclosure material (i.e. fire wrap blanket) to provide clearance to combustibles where a hood penetrates a ceiling has been specifically prohibited by Section 507.10, IMC 2012 because the grease duct enclosure material has not been listed for this use. See Section 506.3.11, IMC 2012 for the hood enclosure requirements.
04/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plumbing drawings that include the changes made to the men's restroom not included in the previously approved plans. Reference: Section 107.2.1, IBC 2012.
2. Provide power for the new water heater. Reference: Sections 303.2 and 607.1, IPC 2012.
3. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
4. Show how the discharge from the dish machine and the cooking appliances will be limited to 140 degrees Fahrenheit or less before entering the indirect waste receptor. Reference: Section701.7, IPC 2012.
5. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
6. Verify that all of the new vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012
04/20/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2020 LBOWERS1 OUT TO CUSTOMER Completed
04/20/2020 LBOWERS1 REJECT SHELF Completed