Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Correct the COMcheck mechanical certificate using the specified unitary air conditioner rather than a packaged terminal air conditioner.
2. Provide a sequence of operation for the restroom exhaust fan.
3. Eliminate the return from the restroom.
4. Install the AC unit per the manufacturer's instructions (e.g. the nominal airflow is 800 CFM for the specified unit).
01/29/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/26/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved