Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM09728
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/29/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Correct the COMcheck mechanical certificate using the specified unitary air conditioner rather than a packaged terminal air conditioner. 2. Provide a sequence of operation for the restroom exhaust fan. 3. Eliminate the return from the restroom. 4. Install the AC unit per the manufacturer's instructions (e.g. the nominal airflow is 800 CFM for the specified unit). |
01/29/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/26/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/05/2019 | KROBLES1 | OUT TO CUSTOMER | Completed |