Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/21/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Revise the location of the sediment trap to be downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2012.
12/27/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The COMcheck Mechanical Compliance Certificate (Sheet M0.01) calls out a chiller and a steam boiler. Is the steam boiler the existing Parker Boiler noted in detail 2/MEP2.01? Where is the chiller located and what are its specifications?
2. Verify that the 8" CMU wall separating the med gas room (142) is rated as a 1-hour fire barrier. Reference: Section 5306.2.1, IFC 2018. Note that the 2018 IFC was adopted by the City of Tucson in July, 2018.
3. Revise the vent design for the med gas room (142) to comply with the requirements of Section 5306.2.1, IFC 2018 (i.e. 2 vents in a wall, one within 6" of the floor and one within 6" of the ceiling and sized per the IFC requirements).