Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T18CM09602
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/29/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/01/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comment. As per the previous electrical comment #1. The feeder size for panel 4caal2 is still not identified on the one line diagram. Ref: 2012 IBC sec 107.2.1, 2011 NEC |
02/05/2019 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/15/2019 | TWEIDEM1 | APPROVAL SHELF | Completed |
02/15/2019 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
02/15/2019 | TWEIDEM1 | REJECT SHELF | Completed |