Permit Number: T18CM09602
Parcel: 12310001C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09602
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM009602 - Tenant Improvement (Medical Outpatient - Commercial)
Building Plan Review (1st Review) Banner Blood Bank
1501 N Campbell Avenue

TRANSMITTAL DATE: January 8, 2019

DUE DATE: January 8, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a review of the tenant improvement plans. While zoning has no comments related to the use as it is an allowed use under the PAD and is an existing building with a proposed improvement of the interior only, zoning cannot approve the TI at this time.

2. COMMENT: Zoning will review the building plans on the next submittal to assure that all PDSD Commercial Plans reviewers have reviewed approved the TI. Once the building plans are approved by all PDSD Commercial Plans reviewers zoning can approve the building plans.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
01/08/2019 LOREN MAKUS ENGINEERING REVIEW Passed
12/12/2018 MARTIN BROWN FIRE REVIEW Approved
12/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.1; Drawing Inventory: Please indicate Sheets G0.1 and G0.6 are included in this set.
2. Sheet G0.1; Drawing Inventory: Sheet G0.14 indicates it is included in this set. That sheet was not located. Please verify.
3. Sheet G0.1; Drawing Inventory: Please indicate Sheet G2.4 is included in this set.
4. Sheet G4.4; Title Block: The title block indicates "Progress Print for Pricing Only". Please revise.
5. Sheet A8.3.4; Elevations 5 and 6: This sheet title indicates Level 3 Elevations, and Elevations 5 and 6 reference Rooms 0350005 East and West. Please verify these elevations are pertinent to the 4th Floor Blood Bank.
6. Sheet A9.5.3; Section 1: The bottom of the section indicates "Third Level". Please verify.
7. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
12/19/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/20/2018 ROBERT SHERRY WATER REVIEW Completed
12/20/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/21/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E1.4.4. General Note 1 makes reference to plan sheet E1.4.0 for feeder schedules. Please include this sheet in this submittal, or revise the feeder legend on Plan Sheet E1.4.4 so that it correlates with the new feeder for panel 4CAAL2.
#2. Ref; Plan Sheet E5.4.1. Mechanical Power Plan. Please identify the scope of work for this plan sheet.
#3. Please provide a legend and symbol plan.
#4. Please provide a complete panel schedule for 4CAAL-S1, include load calcs.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2019 TWEIDEM1 APPROVAL SHELF Completed
01/28/2019 TWEIDEM1 OUT TO CUSTOMER Completed
01/28/2019 TWEIDEM1 REJECT SHELF Completed