Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09602
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM009602 - Tenant Improvement (Medical Outpatient - Commercial) Building Plan Review (1st Review) Banner Blood Bank 1501 N Campbell Avenue TRANSMITTAL DATE: January 8, 2019 DUE DATE: January 8, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has done a review of the tenant improvement plans. While zoning has no comments related to the use as it is an allowed use under the PAD and is an existing building with a proposed improvement of the interior only, zoning cannot approve the TI at this time. 2. COMMENT: Zoning will review the building plans on the next submittal to assure that all PDSD Commercial Plans reviewers have reviewed approved the TI. Once the building plans are approved by all PDSD Commercial Plans reviewers zoning can approve the building plans. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans |
| 01/08/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 12/12/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/19/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.1; Drawing Inventory: Please indicate Sheets G0.1 and G0.6 are included in this set. 2. Sheet G0.1; Drawing Inventory: Sheet G0.14 indicates it is included in this set. That sheet was not located. Please verify. 3. Sheet G0.1; Drawing Inventory: Please indicate Sheet G2.4 is included in this set. 4. Sheet G4.4; Title Block: The title block indicates "Progress Print for Pricing Only". Please revise. 5. Sheet A8.3.4; Elevations 5 and 6: This sheet title indicates Level 3 Elevations, and Elevations 5 and 6 reference Rooms 0350005 East and West. Please verify these elevations are pertinent to the 4th Floor Blood Bank. 6. Sheet A9.5.3; Section 1: The bottom of the section indicates "Third Level". Please verify. 7. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 12/19/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/20/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/20/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/21/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet E1.4.4. General Note 1 makes reference to plan sheet E1.4.0 for feeder schedules. Please include this sheet in this submittal, or revise the feeder legend on Plan Sheet E1.4.4 so that it correlates with the new feeder for panel 4CAAL2. #2. Ref; Plan Sheet E5.4.1. Mechanical Power Plan. Please identify the scope of work for this plan sheet. #3. Please provide a legend and symbol plan. #4. Please provide a complete panel schedule for 4CAAL-S1, include load calcs. Ref; 2012 IBC sec 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/28/2019 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 01/28/2019 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 01/28/2019 | TWEIDEM1 | REJECT SHELF | Completed |