Permit Number: T18CM09506
Parcel: 14027048B

Address:
2825 E GINTER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09506
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2018 ELISA HAMBLIN ZONING REVIEW Approved
12/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a COMcheck envelope compliance report for the building alteration.
2. Provide heating/cooling load calculations for the new fan coil units.
12/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a GFI protected receptacle for HP Maintenance per NEC 210 .63.
#2. Provide a switched luminaire above the ceiling for the FC units per NEC 210.70 (c).
12/05/2018 EHAMBLI1 ENGINEERING REVIEW Passed
12/05/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please review the construction type that has been designated for the building; type III-B construction specifies a fire resistance rating of 2-hr fire resistance rating for exterior walls. IBC TABLE 601
2. Verify the type of construction for the building as type II-B or VB construction. IBC TABLE 601
3. Provide a construction detail for the in-fill portion of the building; specify anchorage of the wall to the slab. IBC 107.2.1
4. Provide a construction of the furr-out wall; indicate anchorage to the slab and existing walls. IBC 107.2.1
5. Two (2) sets of plans are required.

Please provide written responses to all comments.
12/05/2018 ROBERT SHERRY WATER REVIEW Completed
12/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/05/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/05/2018 EHAMBLI1 LANDFILL REVIEW Passed
12/06/2018 MASHFOR1 FIRE REVIEW Approved