Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2018 ANDREW CONNOR ZONING REVIEW Approved
12/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to verify that adequate ventilation will be provided to the new classrooms and offices.Reference: Section 403.3, IMC 2012.
2. Show the air balancing data for the new classrooms and offices. "Comfort balancing" is not acceptable. Reference: Section 107.2.1, IBC 2012 and Section 403.2, IMC 2012.
12/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/05/2018 ACONNOR1 ENGINEERING REVIEW Passed
12/05/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/05/2018 ROBERT SHERRY WATER REVIEW Completed
12/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/05/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/06/2018 MASHFOR1 FIRE REVIEW Approved Deferred Submittal for Fire Sprinklers will be supplied to TFD for review