Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09432
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/03/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/03/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ventilation calculations for the five AC units. 2. Provide the sequence of operation for the CO2 monitoring system. 3. Show the termination poins for the AC condensate drains. |
| 12/03/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/03/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/03/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. CS1 The occupant laod factor for a mercantile occupancy on the ground floor is 30, not 60. IBC 1004.1.2 2. The minimum plumbing fixture calculations must reference IBC TABLE 2902.1 for required number of plumbing fixtures. 3. A1.2 On the plumbing ADA plumbing elevations; please show the vertical grab bar at the water closet location. ICC A117.2 SEC. 604.5 4. A1.3 Provide attachment and structurl details for the water heater brackett; submit load calculations for verification that the brackett will support the water heater. IBC 107.2.1 5. Specify the 2012 IBC for reference of desgin for the structural calculations. IBC 107.2.1 6. S301 Provide hangar specification for DETAIL 1. ibc 107.2.1 7. S3.1 Check the reference to DETAIL 6 which calls out IAPMO ER; should reference ICC . |
| 12/03/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/03/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/21/2018 | AVAUGHN1 | ENGINEERING | REVIEW | Needs Review | |
| 12/21/2018 | AVAUGHN1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/21/2018 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 12/21/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 12/21/2018 | AVAUGHN1 | REJECT SHELF | Completed |