Permit Number: T18CM09372
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09372
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2018 MASHFOR1 FIRE REVIEW Approved
12/14/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/18/2018 ROBERT SHERRY WATER REVIEW Completed
12/18/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that tempered water is supplied to the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide automatic faucets for the restroom lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate at least 10-seconds per cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
12/18/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/27/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved