Permit Number: T18CM09370
Parcel: 12106016B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM09370
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2019 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Denied An application for a Special Exception Land Use (administrative review of Director's Approval Procedure for Wireless Communication Facilities) must be submitted and approved prior to permitting. When Special Exception is approved, submit a copy of the Director's decision letter.
03/18/2019 KROBLES1 COMMUNICATIONS REVIEW Approved
11/30/2018 JVINCEN1 FIRE REVIEW Approved
12/07/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Needs Review Sheets BOM, GN-1, A-1, A-2 are not sealed by the professional registrant. Sheets are required to be sealed in accordance with ARS 32-144.
12/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review Sheets BOM, GN-1, A-1, A-2 are not sealed by the professional registrant. Sheets are required to be sealed in accordance with ARS 32-144.
12/20/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
12/20/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM09370 - Communications Use (Submitted as a swap out)
Sprint Cell Tower (1st Review)
1130 N. Craycroft Road - C-2 Zoning

TRANSMITTAL DATE: December 20, 2018

DUE DATE: December 20, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: After reviewing the proposed plans it appears that 3 new antennas are to be added along with a new Lighting Rod above the allowed or approved 45'-6" height. In addition, an additional ten-foot monopole extension is proposed. While the monopole extension is not exceeding the 45'-6" height the extension and lighting rod is a change from what was originally approved. Further evaluation by Peter McLaughlin is suggested by zoning.

Contact Peter McLaughlin at 520-837-4898 or Peter.McLaughlin@tucsonaz.gov or Susan Montes at 520-8374949 or Susan.montes@tucsonaz.gov for information on the correct process required for this proposal.

2. COMMENT: Once the proposal has been approved through the appropriate process first re-submit the plans to PDSD for review and approval.



If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved SE Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
03/25/2019 AVAUGHN1 APPROVAL SHELF Completed
03/25/2019 AVAUGHN1 OUT TO CUSTOMER Completed
03/25/2019 AVAUGHN1 REJECT SHELF Completed