Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM09301
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09301
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2018 ELISA HAMBLIN ZONING REVIEW Approved
11/27/2018 EHAMBLI1 ENGINEERING REVIEW Passed
11/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/28/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the mechanical design with the kitchen equipment schedule on sheet A13 (e.g. a 60"-long Type II hood is to be installed).
11/28/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/28/2018 MASHFOR1 FIRE REVIEW Approved
11/28/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Is a grease interceptor connected to the mop sink?
2. The hand sinks are not required to be connected to grease waste provided the proper sign is placed on each sink.
3. Does the Turkish coffee maker require a water connection?
11/28/2018 ROBERT SHERRY WATER REVIEW Completed
11/28/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed