Permit Number: T18CM09262
Parcel: 132130840

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09262
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2018 ALEXANDRA HINES ZONING REVIEW Approved
11/26/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Include the ventilation requirements for the work room and rest room in the ventilation calculations
11/26/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide compliance with the 2012 IECC for lighting.
Also show the breaker panel location on the floor plans.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, 2012 IECC.
11/26/2018 AHINES2 ENGINEERING REVIEW Passed
11/26/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Floor Plan: Per the IBC Section 402.4.2.1, tenant spaces must be separated from other tenant spaces by a fire partition per Section 708. Please indicate under Partition Type W4 the construction and fire resistance rating of that wall, and provide a U.L. Listing Number for that partition.
2. Sheet A1.0; Floor Plan: Please indicate the single point of use water dispenser on the plan.
3. General: Please provide written responses to all reveiw comments.
11/26/2018 ROBERT SHERRY WATER REVIEW Completed
11/26/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The minimum plumbing fixture analysis on sheet T1.0 states that a point-of-use water dispenser is provided but the plumbing drawing calls for a drinking fountain to be installed. Clarify what is to be installed and who is to install it.
11/26/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/27/2018 MARTIN BROWN FIRE REVIEW Approved