Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09262
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2018 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 11/26/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Include the ventilation requirements for the work room and rest room in the ventilation calculations |
| 11/26/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide compliance with the 2012 IECC for lighting. Also show the breaker panel location on the floor plans. Ref; 2012 IBC sec 107.2.1, 2011 NEC, 2012 IECC. |
| 11/26/2018 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 11/26/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Floor Plan: Per the IBC Section 402.4.2.1, tenant spaces must be separated from other tenant spaces by a fire partition per Section 708. Please indicate under Partition Type W4 the construction and fire resistance rating of that wall, and provide a U.L. Listing Number for that partition. 2. Sheet A1.0; Floor Plan: Please indicate the single point of use water dispenser on the plan. 3. General: Please provide written responses to all reveiw comments. |
| 11/26/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/26/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The minimum plumbing fixture analysis on sheet T1.0 states that a point-of-use water dispenser is provided but the plumbing drawing calls for a drinking fountain to be installed. Clarify what is to be installed and who is to install it. |
| 11/26/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/27/2018 | MARTIN BROWN | FIRE | REVIEW | Approved |