Permit Number: T18CM09261
Parcel: 13423411A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM09261
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations for the two mini-split AC systems (the unit capacities were provided). [Initial comment: Provide heating and cooling load calculations for the installation of the two ductless mini-split AC systems. Reference: Section C403.2.2, IECC 2012.]
2. Comment not resolved. Specify the termination point for the condensate drains. [Initial comment: Show the size, routing, and termination of the condensate drains for the proposed ductless mini-split AC systems. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.]
01/29/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2019 PMARTIN1 APPROVAL SHELF Completed
03/06/2019 PMARTIN1 OUT TO CUSTOMER Completed
03/06/2019 PMARTIN1 REJECT SHELF Completed