Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/29/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations for the two mini-split AC systems (the unit capacities were provided). [Initial comment: Provide heating and cooling load calculations for the installation of the two ductless mini-split AC systems. Reference: Section C403.2.2, IECC 2012.] 2. Comment not resolved. Specify the termination point for the condensate drains. [Initial comment: Show the size, routing, and termination of the condensate drains for the proposed ductless mini-split AC systems. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.] |
01/29/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/25/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |