Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM09261
Parcel: 13423411A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09261
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2018 MARTIN BROWN FIRE REVIEW Approved
12/10/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CS; Plumbing Facilities: Please provide the total occupant load, the men's occupant load, and the women's occupant load. Using the IBC Table 2902.1, please indicate the required number of water closets, lavatories, drinking fountains, and service sinks.
2. Sheet A-0.1; Symbol Legend: Please indicate how the number of allowable occupants were derived at each exit (765, 230, and 170) using the IBC Section 1005.
3. Sheet A-0.1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the Symbol Legend.
4. Sheet A-1.1; Floor Plan: Are the two rooms near grids A and 5 new (indicated with dark walls), or are these shown in error? Please verify.
5. Sheet A-3.1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise Elevation 10.
6. Sheet A-3.2; Detail 6C: Please indicate the braces at the top of the wall and reference Detail 10/A-3.2.
7. Sheet A-3.2; Section 10: Please indicate the brace size and connection (size and quantity) to the wall and to the roof above.
8. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
12/17/2018 ROBERT SHERRY WATER REVIEW Completed
12/17/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that tempered water is supplied to the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide automatic faucets for the restroom lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate at least 10-seconds per cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
12/17/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations for the installation of the two ductless mini-split AC systems. Reference: Section C403.2.2, IECC 2012.
2. Show the size, routing, and termination of the condensate drains for the proposed ductless mini-split AC systems. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
12/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved