Permit Number: T18CM09245
Parcel: 119032170

Address:
443 W 41ST ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T18CM09245
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2019 NICHOLAS ROSS ZONING REVIEW Approved P&DS TRANSMITTAL


FROM: Nick Ross
Lead Planner

PROJECT:
T18CM09245
443 W. 41st St.
Addition and Permit Existing Structure



TRANSMITTAL: December 19, 2018


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).
The applicant is permitting an existing structure on the south side of the property and proposing a new addition. The height of the structure on the south side is 19'2" and has a setback of 5'0". The required setback is 12'6". The new addition is proposed to be 20'10" with a setback of 8'0" on the west side of the property and 4'6" on the east side. The required setback is 13'7". DDO is required.
04/12/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
12/19/2018 NROSS1 NPPO REVIEW Passed
12/19/2018 NROSS1 ENGINEERING REVIEW Passed