Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM09214
Parcel: 13324010C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09214
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide an electrical plan showing all electrical power and lighting to be modified. Include locations of all outlets, luminaires, luminaire schedule, branch circuit and panel designations, complete panel schedule, Arc fault protection as required per NEC art 210. 2012 IECC code compliance if applicable.
Is the power and lighting typical for all units?
Ref: 2012 IBC sec. 107.2.1, 2011 NEC art. 408.4, City of Tucson Commercial Plan Submittal Requirements.
11/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Project Data: The Project Intent indicates the Villa 2 remodel of 11 units for assisted living. The Table on this sheet indicates these are an R-1 occupancy classification, while Section 310 of the IBC defines the R-1 group as transient occupants. Please verify if occupants are non-transient or transient, and if R-1 is the correct occupancy classification.
2. Sheet A1.0; Project Data: Please indicate on this sheet the total square footage of the 11 units in this project, and the total occupant load in those units.
3. Sheet A2.0; Typical Floor Plan: A note at the shower indicates grab bars. Sheet A3.0 indicates those grab bars in the elevations. Please verify the grab bars shown on the Elevations "B" and "C" meet the requirements as indicated in the ICC/ANSI Section 608.
4. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
11/26/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1.Provide a mechanical plan (e.g. duct revisions, air balancing data, etc.).
2. Show how ventilation will be provided. Reference: Section 403.3, IMC 2012 and Section R403.5, IECC 2012.
11/26/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a plumbing design (e.g. show the cold water, hot water, drain, and vent piping as well as typical riser diagrams).
11/26/2018 EHAMBLI1 ENGINEERING REVIEW Passed
11/26/2018 ELISA HAMBLIN ZONING REVIEW Approved
11/26/2018 ROBERT SHERRY WATER REVIEW Completed
11/26/2018 MARTIN BROWN FIRE REVIEW Approved