Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a design for the fan coil mounting shelf noted on sheet M2.1.
2. Provide a sequence of operation for the refrigerant detection, ventilation, and emergency shut-off system for the mechanical room.
3. Provide fire safing for the pipe penetrations of the floor-ceiling assembly.
11/26/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise detail 8/M4.1 to show the shut off valve located upstream of the dirt leg. Reference: Section 408.4, IFGC 2012.
11/26/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a detailed wiring diagram and show wiring methods to indicate the installation and operation of the Emergency Power Off buttons for the equipment.
#2. Indicate any new wiring required for the installation of the mechanical equipment.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 300, City Of Tucson Commercial Plan Submittal Requirements (Electrical) www.tucsonaz.gov/pdsd.
11/26/2018 MARTIN BROWN FIRE REVIEW Approved