The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM09180
Parcel: 11706243B

Address:
236 E 12TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM09180
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2019 AVAUGHN1 ZONING REVIEW Needs Review
01/23/2019 AVAUGHN1 ENGINEERING REVIEW Needs Review
01/23/2019 AVAUGHN1 BUILDING-COMMERCIAL REVIEW Needs Review
01/23/2019 AVAUGHN1 FIRE REVIEW Needs Review
01/23/2019 AVAUGHN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/20/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an energy code analysis of the building alterations (e.g. REScheck or COMcheck).
2. Provide mechanical ventilation per Section 403.3, IMC 2012.
11/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. 120 volt receptacles to be Tamper Resistant. NEC 406.
#2. Provide ARC Fault protected branch circuits as required per NEC 210.
#3. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting.
#4. Compliance with the 2012 IECC for lighting.
#5. Provide a maintenance receptacle on the roof for the mechanical equipment. NEC 210.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, 2012 IECC, Tucson Outdoor Lighting Code.
11/20/2018 ROBERT SHERRY WATER REVIEW Passed
11/20/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the calculations used to determine the size of the water distribution pipes.
2.Clarify the scope of work for the shower.
3. Show the existing drain piping and the modifications.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/23/2019 AVAUGHN1 APPROVAL SHELF Completed
01/23/2019 AVAUGHN1 OUT TO CUSTOMER Completed
01/23/2019 AVAUGHN1 REJECT SHELF Completed