Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM09180
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2019 | AVAUGHN1 | ZONING | REVIEW | Needs Review | |
| 01/23/2019 | AVAUGHN1 | ENGINEERING | REVIEW | Needs Review | |
| 01/23/2019 | AVAUGHN1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/23/2019 | AVAUGHN1 | FIRE | REVIEW | Needs Review | |
| 01/23/2019 | AVAUGHN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/20/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an energy code analysis of the building alterations (e.g. REScheck or COMcheck). 2. Provide mechanical ventilation per Section 403.3, IMC 2012. |
| 11/20/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. 120 volt receptacles to be Tamper Resistant. NEC 406. #2. Provide ARC Fault protected branch circuits as required per NEC 210. #3. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. #4. Compliance with the 2012 IECC for lighting. #5. Provide a maintenance receptacle on the roof for the mechanical equipment. NEC 210. Ref; 2012 IBC sec 107.2.1, 2011 NEC, 2012 IECC, Tucson Outdoor Lighting Code. |
| 11/20/2018 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 11/20/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the calculations used to determine the size of the water distribution pipes. 2.Clarify the scope of work for the shower. 3. Show the existing drain piping and the modifications. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/23/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 01/23/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 01/23/2019 | AVAUGHN1 | REJECT SHELF | Completed |